Screenshot 2023-03-01 145210

YMGI PTAC-xxx-x2xxx & PTHP-xxx-x4xxx PTAC Configuration Guide

 

Remote Thermostat Interface

Remote Thermostat Interface Image

Screw Terminal

5cc685ee-ba59-4917-a4df-695af7f80e36

PTAC-xxx-x2xxx & PTHP-xxx-x4xxx Series Remote Thermostat Enable:

 

Steps

Image

1

Unplug the PTAC

 

2

Move dip switch 2 into the UP position

33241d88-4884-4e33-b3f0-205366b71805

 

3

Plug the PTAC back in

 

 

AN40400 - Screw terminal PTAC wiring harness color coding guide:

***Unused Anacove Wiring Harness wires should be removed from the Wiring Harness. Cut the wire off approximately 1/2" from the HVAC Controller end of the harness***

Anacove Wire Color

PTAC-xxx-x2xxx & PTHP-xxx-x4xxx Remote Thermostat Interface

Red

R

Black

C

White

W

Yellow

Y

Green

GL

Brown

GH

Blue

Not Used

Orange

O