Islandaire EZxxxxGSxxxxxxx PTAC Configuration Guide
Remote Thermostat Interface |
Remote Thermostat Interface Image |
Pin Header |
![]() |
EZxxxxGSxxxxxxx Remote Thermostat Enable:
Step |
Image |
|
1 |
Turn PTAC off on user controls |
![]()
|
2 |
Press and hold the MODE and WARM buttons simultaneously for 3 seconds |
A buzzer will chime |
3 |
The display should read "r" |
If the display reads "P" then repeat step 2 until it reads "r" |
AN40400 - Screw terminal PTAC wiring harness color coding guide:
***Unused Anacove Wiring Harness wires should be removed from the Wiring Harness. Cut the wire off approximately 1/2" from the HVAC Controller end of the harness***
Anacove Wire Color |
EZxxxxGSxxxxxxx Remote Thermostat Interface Wire Color |
Red |
R/RED |
Black |
C/BLACK |
White |
W/WHITE |
Yellow |
Y/YELLOW |
Green |
GL/ORANGE |
Brown |
GH/GREEN |
Blue |
B/BLUE |
Orange |
Not Used |