Screenshot 2023-03-01 145210

GE AZ45E & AZ65H PTAC Configuration Guide

 

Remote Thermostat Interface

Remote Thermostat Interface Image

Pin Header

These models could use an Anacove GE 7-Pin or a GE 8-Pin Wiring Harnesses

Check the Remote Thermostat Connector Socket port to confirm the number of pins and the proper wiring harness to utilize

0d1d21ce-b2bc-409b-87d4-d89b42b43a9d

 

AZ45E & AZ65H Series Remote Thermostat Enable:

***If after pressing the red Aux Set button the user interface begins to flash it means that the display controls have been locked out. In order to correct this, hold down the Display button for 10 seconds***

 

Steps

Image

1

Turn the unit off at the control panel. The unit needs power but the On/Off button should be off

 

2

Lift the front cover off and press the red Aux Set button

e74ec749-f758-4107-bac3-13b83a7c175e

3

Press the mode button until the first digit of the LED display reads "6"

b85ec9dc-fa09-4761-acf4-9b357ecab412

4

Press the + button until the digit next to the 6 is an "n"

938ee739-5e25-474b-86d1-6956b843fa0b

5

Press the red Aux Set button to save the Use Wall Thermostat setting

 

6

The backlit display should read "Use Wall Thermostat" to confirm the sequence was completed successfully

e0196f36-8f30-4d8e-9cd5-d2d96eb8dddb

 

 

GE PTAC HVAC Controller Gateway Mounting Placement

GE AZ45 & AZ65 Mounting Placement