GE AZ41E & AZ61H PTAC Configuration Guide
Remote Thermostat Interface |
Remote Thermostat Interface Image |
Screw Terminal |
![]() |
GE AZ41E & AZ61H Series Remote Thermostat Enable:
Steps |
Image |
|
1 |
Turn the unit off at the control panel. The unit needs power but the On/Off button should be off |
|
2 |
Lift the front cover off and press the red Aux Set button |
![]() |
3 |
Press the mode button until the first digit of the LED display reads "6" |
![]() |
4 |
Press the + button until the digit next to the 6 is an "n" |
![]() |
5 |
Press the red Aux Set button to save the Use Wall Thermostat setting |
|
6 |
The backlit display should read "Use Wall Thermostat" to confirm the sequence was completed successfully |
![]() |
AN40400 - Screw terminal PTAC wiring harness color coding guide:
***Unused Anacove Wiring Harness wires should be removed from the Wiring Harness. Cut the wire off approximately 1/2" from the HVAC Controller end of the harness***
Anacove Wire Color |
AZ41E & AZ61H Remote Thermostat Interface |
Red |
R |
Black |
C |
White |
W |
Yellow |
Y |
Green |
GL |
Brown |
GH |
Blue |
B |
Orange |
Not Used |