Friedrich VHAxxxxxRTN-x VTAC Configuration Guide
***The HVAC Controller Gateway should always be mounted as close to the return of the VTAC as possible***
***These units require the installation of an additional 24VAC transformer be installed in order to properly power the Anacove HVAC Controller Gateway. The transformer should be an appropriate transformer for either the 230/208V or 265V that the VTAC is. Reference the below section about wiring for how to wire these up***
|
Remote Thermostat Interface |
Remote Thermostat Interface Image |
|
Screw Terminal |
|
VHAxxxxxRTN-x Series Remote Thermostat Enable:
|
Steps |
|
|
1 |
There are no configuration settings to be made as the VTAC is always in remote thermostat mode |
AN40400 - Screw Terminal Wiring Harness color coding guide:
***Unused Anacove Wiring Harness wires should be removed from the Wiring Harness. Cut the wire off approximately 1/2" from the HVAC Controller end of the harness***
|
Anacove Wire Color |
VHAxxxxxRTN-x Remote Thermostat Interface |
24V Transformer Wire Color |
|
Red (connect via wire/lever nut) |
N/A |
Red (connect via wire/lever nut) |
|
Black (connect via wire/lever nut) |
C (connect via wire/lever nut) |
Black (connect via wire/lever nut) |
|
White |
W |
N/A |
|
Yellow |
Y |
N/A |
|
Green |
GL |
N/A |
|
Brown |
GH |
N/A |
|
Blue |
B |
N/A |
|
Orange (not used) |
N/A |
N/A |