Screenshot 2023-03-01 145210

Friedrich PZExxxxxB-x & PZHxxxxxB-x PTAC Configuration Guide

 

Remote Thermostat Interface

Remote Thermostat Interface Image

Screw Terminal

ed69a74e-e544-4ad5-bd25-e160dd88b359

 

PZExxxxxB-x & PZHxxxxxB-x Series Remote Thermostat Enable:

 

Steps

1

Turn the unit off at the user controls. The unit needs power but the power button should be off

2

Hold the "COOL" and "UP" buttons at the same time for 5 seconds

3

The display will read "r" and beep twice confirming that the sequence was performed successfully

 

AN40400 - Screw terminal PTAC wiring harness color coding guide:

***Unused Anacove Wiring Harness wires should be removed from the Wiring Harness. Cut the wire off approximately 1/2" from the HVAC Controller end of the harness***

Anacove Wire Color

PZExxxxxB-x & PZHxxxxxB-x Remote Thermostat Interface

Red

R

Black

C

White

W

Yellow

Y

Green

GL

Brown

GH

Blue

B

Orange

Not Used

 

 

Friedrich PTAC HVAC Controller Gateway Mounting Placement

Friedrich 5