Screenshot 2023-03-01 145210

Fan Coil With 2 Speed Fan Configuration Guide

 

 

***The HVAC Controller Gateway should always be mounted as close to the return of the Fan Coil as possible.***

Fan Coil Remote Thermostat Enable:

 

Step

1

There are no configuration settings to be made as a fan coil is always in remote thermostat mode

 

Screw Terminal Wiring Harness color coding guide:

***Maximum output drive is 1 amp. Use an external relay if higher current is required.***

***Unused Anacove Wiring Harness wires should be removed from the Wiring Harness. Cut the wire off approximately 1/2" from the HVAC Controller end of the harness***

Anacove Wire Color

Fan Coil Remote Thermostat Interface/Wiring

Red

24VAC

Black

Common

White

Heat Valve or Electric Heat

Yellow

Cool Valve

Green

Low Fan

Brown

High Fan

Blue

Not Used

Orange

Not Used