Screenshot 2023-03-01 145210

Enviroair PTAC 1642-xxC-x & PTAC 1642-xxH-x PTAC Configuration Guide

 

Remote Thermostat Interface

Remote Thermostat Interface Image

Screw Terminal

15f5bc0f-7baa-4686-b83b-d1657ec13684

 

PTAC 1642-xxC-x & PTAC 1642-xxH-x Remote Thermostat Enable:

 

Step

Image

1

Unplug the PTAC from power

 

2

Remove the two screws on the metal plate that covers the Remote Thermostat Interface of the PTAC

Screenshot 2025-04-25 141213

3

Move dip switch S3 to UP (ON) and move dip switch S9 to DOWN (OFF). Make sure dip switches S4 and S5 are in the UP (ON) position as well

Screenshot 2025-04-25 140703

4

Wire up the Anacove Screw Terminal Wiring Harness wires to the PTAC's Remote Thermostat Interface according to the below color coding guide

PTAC Remote Thermostat Interface terminals HEAT2, FC(N), and FC(L) are not used and should have no wires connected to them

5

Reattach the metal plate that covers the Remote Thermostat Interface of the PTAC

 

6

Plug the PTAC back into power

 

 

AN40400 - Screw terminal PTAC wiring harness color coding guide:

***Unused Anacove Wiring Harness wires should be removed from the Wiring Harness. Cut the wire off approximately 1/2" from the HVAC Controller end of the harness***

Anacove Wire Color

PTAC 1642-xxC-x & PTAC 1642-xxH-x Remote Thermostat Interface

Red

24V(L)

Black

24V(N)

White

HEAT 1

Yellow

COMP

Green

LOW-FAN

Brown

HI-FAN

Blue

4-WAY

Orange

Not Used

 

 

Enviroair PTAC HVAC Controller Gateway Mounting Placement

thumbnail_IMG_3672